System Specifications
|
|
DETECTOR TYPE
|
Infrared
absorption type
|
|
MEASURING RANGE
|
0 to 100%
LEL
0 to 100%
by volume (methane only)
|
|
GASES
|
Methane,
propane, ethane, ethylene, butane, hexane, pentane Consult factory for other gases
|
|
DETECTOR LIFE
|
Greater than
5 years
|
|
ACCURACY
@ 25°C
|
± 3% LEL
at = 50% LEL reading
± 5% LEL
at > 50% LEL reading
|
|
ZERO DRIFT
|
< 2% per
year
|
|
RESPONSE TIME
WITH SPLASH
GUARD
|
T50 = 1.5
s, T60 = 1.5 s, T90 = 3 s
Except ethylene where T60 = 2 s and T90 = 4 s
|
|
READOUT/RELAY DISPLAY MODULES
|
DC110; TA102A;
IR4000 display, and relay alarms
|
|
ACCESSORIES
|
Junction
box, duct mount junction box, calibration cup, flow block, splash guard, rain
guard, portable purge calibrator
|
|
CLASSIFICATION
|
Class I,
Zone 1, IIB + H2 (Ta=-40° C to +75° C) Ex d, IIB + H2 T5 Gb
Ex tb
IIIC, T100° C Db, IP66 (Ta=-60° C to +75° C)
|
|
WARRANTY
|
Two years
|
|
APPROVALS
|
ATEX, IECEx,
MED, DNV GL, CE,
FM 6310,
6320 and CSA 22.2 No. 152
EN 60079-29-1
Performance Approved HART Registered, SIL 3 suitable
FM Certified
to IEC 61508
|
|
Environmental Specifications
|
|
OPERATING TEMPERATURE RANGE
FM, CSA,
GOST-R
ATEX, IECEx
ETHYLENE
|
-40° F to
+167° F (-40° C to +75° C)
-76° F to
+167° F (-60° C to +75° C)
-40° F to
+140° F (-40° C to +60° C)
|
|
STORAGE TEMPERATURE RANGE
|
-58° F to
+185° F (-50° C to +85° C)
|
|
OPERATING HUMIDITY RANGE
|
10% to 95%
RH, non-condensing
|
|
Electrical Specifications
|
|
INPUT POWER
|
20-36 VDC
@ 200 mA max.
24 VDC nominal
|
|
ANALOG SIGNAL START UP, FAULT (non-HART)
START UP, FAULT (HART)* CAL, ZERO,
GAS CHECK*
DIRTY
OPTICS* 0 TO 100% LEL OVER-RANGE
|
0-21.7 mA
(600 ohms max.)
0 mA
1.25 mA
1.5 mA
2.0 mA
4 to 20 mA
(proportional)
20 to 21.7
mA
|
|
EMC
|
Complies
with EN 50270, EN 61000-6-4
|
|
CABLE REQUIREMENTS
|
Max.
distance between IR400 and power source @ 24 VDC nominal (20 ohm loop resistance):
14 AWG (2.0
mm2) - 3600 ft (1100 m)
Max. distance
for analog output (500 ohms max): 14 AWG (2.0 mm2) - 9000 ft. (2740 m)
|
|
FAULTS MONITORED
|
Re-calibration
error, EPROM checksum error, optics failure/blockage; low supply voltage, EEPROM
checksum error, reference or active lamp failure, heater failure, time to re-zero
unit, short circuit on CAL_IO wire
|
|
RS-485 OUTPUT
|
Modbus RTU,
suitable for linking up to 128 units or up to 247 units with repeaters
|
|
BAUD RATE
|
2400, 4800,
9600, or 19200 BPS
|
|
HART (OPTIONAL)
|
HART 6, HART
Device Descriptor available. AMS aware
|
|
WIRELESS COMMUNICATION
|
Available
with ELPRO Technologies wireless devices
|
|
Mechanical Specifications
|
|
|
DIAMETER
|
2.9” (74
mm)
|
|
LENGTH
|
8.87” (225
mm)
|
|
WEIGHT ALUMINUM STAINLESS STEEL
|
3 lbs (1.35
kg)
6 Ibs (2.7
kg)
|
|
MOUNTING
|
¾" NPT
|
|
INGRESS PROTECTION
|
Type 4X,
IP66
|
|
HOUSING
|
Aluminum
6061-T6 alloy or 316 stainless steel
|
|
STANDARD CONFIGURATION
|
IR400-0-01-1-2-0-1-0
Methane,
4-20 mA, Modbus, aluminum, splashguard w/screen, no junction box
|