YTA610-JA1A4NN/KU2 | Series YTA610 | Temperature Transmitter | Yokogawa
YTA610-JA1A4NN/KU2 | Series YTA610 | Temperature Transmitter | Yokogawa

YTA610-JA1A4NN/KU2 | Series YTA610 | Temperature Transmitter | Yokogawa

0 Review(s)
Availability: Estimated Lead Time: 12 - 16 Weeks
Part Number: YTA610-JA1A4NN/KU2
$528.00
Retail Price:$621.00
You Save:$93.00(15%)
Brand / Manufacturer : Yokogawa
Categories : Transmitter
Shipping Weight : 5kg
Condition : New with 1 year warranty
Write a Review
YTA610-JA1A4NN/KU2 | Series YTA610 | Temperature Transmitter | Yokogawa

Model and Suffix Codes :
  • Model: YTA610 - Temperature Transmitter
  • Output signal: -J - 4 to 20 mA DC with digital communication HART 7 protocol
  • A: Always A
  • Sensor input: 1 - Single
  • Housing code: A - Aluminium
  • Electrical code: 4 - M20 female
  • Integral indicator: N - None
  • Mounting bracket: 
  • Option Codes: 
    KU2: ATEX
    4-20 mA:
    [Intrinsically safe approval]
      Applicable Standard: EN 60079-0; 2012+A11:2013, EN 60079-11:2012
      Certificate No. FM16ATEX0019X
      II 1 G Ex ia IIC T5...T4 Ga
      Ambient Temperature: -40 to 70°C for T4, -40 to 50°C for T5
      Enclosure: IP66/IP67 in accordance with only IEC 60529
      Entity Parameters:
      Supply/Output circuit: Ui=30V, li=200mA, Pi=1.0W, Ci-22nF, Li=0mH
      Sensor circuit: Uo=6V, Io=90mA, Po=135mW, Co=10µF, Lo=3.9mH
      Dielectric strength: 500 V a.c.r.m.s., 1 min
      [+, -, C, 1, 2, 3, 4, 5] to Earth terminal
      [+, -, C] to [1, 2, 3, 4, 5]
    [Flameproof and Dust Ignition Proof Approval]
      Applicable Standard: EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-31:2014
      Certificate: KEMA 07ATEX0130
      II 2 G Ex db IIC T6/T5 Gb, II 2 D Ex IIIC T70°C/T90°C Db
      Ambient Temperature for Gas Atmospheres: -40 to 75°C for T6, -40 to 80°C for T5
      Ambient Temperature for Dust Atmospheres: -30 to 65°C for T70°C, -30 to 80°C for T90°C
      Enclosure: IP66/IP67
      Electrical Connection: 1/2 NPT female and M20 female²

NOTE:
  1. For flat-panel mounting, please prepare bolts and nuts.
  2. Applicable for Electrical Connection Code 2 and 4.

  • Estimated Lead Time: 12 - 16 Weeks
  • Shipping Weight: 5 Kg