General specifications |
Signal type | Analog input |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 2 |
Supply |
Connection | terminals 14+, 15- or power feed module/Power Rail |
Rated voltage | 20 ... 30 V DC |
Ripple | within the supply tolerance |
Power dissipation | = 0.8 W |
Power consumption | max. 0.8 W |
Interface |
Programming interface | programming socket |
Input |
Connection side | field side |
Connection | terminals 1, 2, 3; 4, 5, 6 |
RTD | type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995) type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94) type Cu10, Cu50, Cu100 (P50353-92) type Ni100 (DIN 43760) |
| Measuring current | approx. 200 µA with RTD |
| Types of measuring | 2-, 3-wire connection |
| Lead resistance | max. 50 O per line |
| Measurement loop monitoring | sensor breakage, sensor short-circuit |
Thermocouples | type B, E, J, K, N, R, S, T (IEC 584-1: 1995) type L (DIN 43710: 1985) type TXK, TXKH, TXA (P8.585-2001) |
| Cold junction compensation | external and internal |
| Measurement loop monitoring | sensor breakage |
Potentiometer | 0 ... 20 kO (2-wire connection), 0.8 ... 20 kO (3-wire connection) |
Voltage | selectable within the range -100 ... 100 mV |
Input resistance | = 1 MO (-100 ... 100 mV) |
Output |
Connection side | control side |
Voltage output | 0 ... 5 V or 1 ... 5 V ; output resistance: = 5 O ; load: = 10 kO |
Connection | output I: terminals 7-, 8+ output II: terminals 10-, 11+ |
Fault signal | downscale 0 V or 0.5 V, upscale 5.375 V |
Transfer characteristics |
Deviation | |
| After calibration | Pt100: ± (0.06 % of measurement value in K + 0.1 K (4-wire connection)) thermocouple:
± (0.05 % of measurement value in °C + 1 K (1.2 K for types R and S)) ,
includes ± 0.8 K fault of the cold junction compensation (CJC) mV: ± 50 µV potentiometer: ± 0.05 % of full scale, (excludes faults due to lead resistance) output: 1 to 5 V output: ± 4 mV from 0 to 103.1 % of span; 0 to 5 V output: ± 4 mV from 0.3 to 102.5 % of span |
| Influence of ambient temperature | Pt100: ± (0.0015 % of measurement value in K + 0.0075 % of span)/K ?Tamb*) thermocouple: ± (0.02 K + 0.005 % of measurement value in °C + 0.0075 % of span)/K ?Tamb*) , influence of cold junction compensation (CJC) included: mV: ± (0.01 % of measurement value + 0.0075 % of span)/K ?Tamb*) potentiometer: ± 0.0075 % of span/K ?Tamb*) *) ?Tamb = ambient temperature change referenced to 23 °C (296 K) |
| Influence of supply voltage | < 0.01 % of span |
Reaction time | worst case value (sensor breakage and/or sensor short circuit detection enabled) mV:
1.2 s, thermocouples with CJC: 1.4 s, thermocouples with fixed ref.
temp: 1.4 s, 3- or 4-wire RTD: 1.1 s, 2-wire RTD: 920 ms, Potentiometer:
3-wire connection 2.8 s, 2-wire connection 2.25 s |
Galvanic isolation |
Output/supply, programming input | functional insulation, rated insulation voltage 50 V AC There is no electrical isolation between the programming input and the supply. The programming cable provides galvanic isolation so that ground loops are avoided. |
Indicators/settings |
Display elements | LEDs |
Configuration | via PACTware |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility | NE 21:2006 |
Degree of protection | IEC 60529:2001 |
Protection against electrical shock | UL 61010-1:2004 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 130 g |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-type examination certificate | CESI 04 ATEX 143 |
| Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
| Input | Ex ia |
Inputs | terminals 1, 2, 3, 4, 5, 6 (for passive equipment) |
| Voltage Uo | 9 V |
| Current Io | 22 mA |
| Power Po | 50 mW |
Analog outputs, power supply, collective error | |
| Maximum safe voltage | 250 V (Attention! This is not the rated voltage.) |
Interface | |
| Maximum safe voltage | 250 V (Attention! The rated voltage is lower.), RS 232 |
Certificate | TÜV 02 ATEX 1797 X |
| Marking | II 3G Ex nA II T4 |
Galvanic isolation | |
| Input/Other circuits | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000 |